Inverter
High Frequency Inverter
6.2kW-12kW high frequency inverter
On-grid and Off-grid high frequency inverter.
The inverter adopts mcu microprocessor full digital spwm controltechnology and pure sine wave output.Unique dynamic current loop control technology.
High efficiency, low noise, environmental protection and energysaving.
Automatic switching, enabling unattended operation.Built-in solar charge controller with wide voltage range andultra-high current performance.
PRODUCT PARAMETERS
| Model | CON-INV6.2kW stand-alone series |
CON-INV12kW stand-alone series |
| Parallel Mode | ||
| Allowed number of parallel machines | none/1~6 sets | none/1~6 sets |
| AC Main Grid mode | ||
| Rated input voltage | 230Vac±5% | |
| Input voltage range | (170Vac~280Vac)±2% (90Vac~280Vac)±2% | |
| Frequency | 50Hz/60Hz (auto detection) | |
| Frequency range | 47±0.3Hz~55±0.3Hz(50Hz)57±0.3Hz~65±0.3Hz(60Hz) | |
| Overload / short circuit protection | breaker | |
| Max. efficiency | >95% | |
| Conversion time (Bypass and inverter) |
10ms (typical) | |
| Max. bypass overload current | include | |
| Atmospheric pressure | 40A | 60A |
| Inverter mode | ||
| Output voltage waveform | pure sine wave | |
| Rated output power | 6200VA/6200W | 12000VA/12000W |
| Rated output voltage | 230Vac | |
| Output voltage error | 50Hz±0.3Hz/60Hz±0.3Hz | |
| Output frequency range (Hz) | >92% | >93% |
| Inverter mode | ||
| Overload protection | (102%<Load<125%)±10%: Report error and turn off output after 5 minutes;(125%<load<150%)10%: Report an error and turn off the output after 10 seconds;(Load>150%)10%: Report an error and tum off the output after 5 seconds. | |
| Peak Power | 11000VA | 22000VA |
| Load motor capacity | 3HP |
7HP |
| Output short circuit protection | breaker | |
| Bypass circuit breaker specifications | 40A | 63A |
| Rated battery input voltage | 48V(min. starting voltage 44V) | |
| Battery voltage range | 40.0Vdc-60dc.6Vdc (undervoltage alarm / shutdown volage / overvoltage alarm / overvoltage recovery, LCD screen can be set) |
|
| Power saving mode | Enter power saving mode when load ≤50W | |
| Mains power charging | ||
| Battery Type | lithium battery | |
| Max. charging current (can be set) | 60A | 150A |
| Charging current error | ±5Adc | |
| Charging voltage range | 40~60Vdc | |
| Short circuit protection | Circuit breaker and expulsion fuse | |
| Circuit breaker specifications | 40A | 63A |
| Solar Charging | ||
| MPPT channel number | 1 | 2 |
| Max. PV open circuit voltage | 500Vdc | |
| PV operating voltage range | 100-500Vdc | 80-500Vdc |
| MPPT voltage range | 120-450Vdc | 90-450Vdc |
| Battery voltage range | 40~60Vdc | |
| Max. PV input power | 6200W | 9000W+9000W |
| Max. PV input current | 22A | 27A+27A |
| Solar charging current range (configurable) | 0-100A | 0-150A |
| Charging short circuit protection | Expulsion fuse | |
| Wiring protection | Reverse connection protection | |
| Max. hybrid charging current (PV+AC) | 0-100A | 0-150A |
| Certification Specifications | CE(IEC62109-1,2); EN61000,C2 | |
| EMC certification level | -15°C~55°C, derating operation at >45°C | |
| Operating temperature range | -25°C~55°C | |
| Storage temperature range | 5%~95% (Protection by three-proof paint) | |
| Humidity range | Forced air cooling, adjustable wind speed | |
| Heat dissipation | USB/RS485(WiFi/GPRS)/dry node control | |
| Size (L*W*D) | 460*305*115mm | 540*350*120mm |
| Weight (KG) | 10.8KG | 20KG |